Voltage Drop Calculator
On this page
Calculate
Select the nominal system voltage for the circuit
Select single-phase or three-phase circuit configuration
Enter the expected load current in amperes
Enter the one-way distance from the panel to the load
Select conductor size and material — resistance values in ohms per 1000 ft (NEC Chapter 9 Table 8, 75°C)
Number of conductors per phase (parallel runs reduce effective resistance)
Overview
A Voltage Drop Calculator estimates how much voltage is lost along a conductor run under load. This calculator takes the selected conductor resistance, applies the correct system multiplier for the circuit type, calculates voltage drop in volts, converts that result into a percentage of system voltage, and calculates the voltage available at the load. It is useful for branch-circuit planning, feeder review, and conductor comparisons.
NEC-oriented design guidance commonly references about 3% voltage drop on a branch circuit and 5% maximum total including feeder plus branch circuit as a practical target for reasonable efficiency of operation.
This calculator is intended as a practical estimation tool for circuit planning, conductor sizing verification, and preliminary electrical design. It does not replace detailed engineering analysis that accounts for conductor temperature, conduit fill, ambient conditions, or AC impedance effects.
How to Use This Calculator
Select system voltage — choose from 120 V, 208 V, 240 V, 277 V, 480 V, or 600 V.
Select phase configuration — choose from Single-Phase, Three-Phase.
Enter load current — in A.
Enter one-way wire length — in m (Metric) or ft (Imperial).
Select conductor size and material — resistance values are shown in Ω/1000 ft.
Select conductors per phase — choose from 1, 2, 3, or 4.
Click "Calculate" — get voltage drop, voltage drop percentage, voltage at load.
Inputs & Outputs
Inputs
- •System Voltage — Options: 120 V, 208 V, 240 V, 277 V, 480 V, 600 V
- •Phase Configuration — Options: Single-Phase, Three-Phase
- •Load Current (A)
- •One-Way Wire Length (m / ft)
- •Conductor Resistance — Options: 14 AWG Copper — 3.14 Ω/1000 ft, 12 AWG Copper — 1.98 Ω/1000 ft, 10 AWG Copper — 1.24 Ω/1000 ft, 8 AWG Copper — 0.778 Ω/1000 ft, 6 AWG Copper — 0.491 Ω/1000 ft, 4 AWG Copper — 0.308 Ω/1000 ft, 3 AWG Copper — 0.245 Ω/1000 ft, 2 AWG Copper — 0.194 Ω/1000 ft, 1 AWG Copper — 0.154 Ω/1000 ft, 1/0 AWG Copper — 0.122 Ω/1000 ft, 2/0 AWG Copper — 0.0967 Ω/1000 ft, 3/0 AWG Copper — 0.0766 Ω/1000 ft, 4/0 AWG Copper — 0.0608 Ω/1000 ft, 250 kcmil Copper — 0.0515 Ω/1000 ft, 300 kcmil Copper — 0.0429 Ω/1000 ft, 350 kcmil Copper — 0.0367 Ω/1000 ft, 500 kcmil Copper — 0.0258 Ω/1000 ft, 12 AWG Aluminum — 5.17 Ω/1000 ft, 10 AWG Aluminum — 3.25 Ω/1000 ft, 8 AWG Aluminum — 2.04 Ω/1000 ft, 6 AWG Aluminum — 1.29 Ω/1000 ft, 4 AWG Aluminum — 0.808 Ω/1000 ft, 3 AWG Aluminum — 0.642 Ω/1000 ft, 2 AWG Aluminum — 0.510 Ω/1000 ft, 1 AWG Aluminum — 0.404 Ω/1000 ft, 1/0 AWG Aluminum — 0.321 Ω/1000 ft, 2/0 AWG Aluminum — 0.254 Ω/1000 ft, 3/0 AWG Aluminum — 0.201 Ω/1000 ft, 4/0 AWG Aluminum — 0.160 Ω/1000 ft, 250 kcmil Aluminum — 0.135 Ω/1000 ft, 300 kcmil Aluminum — 0.113 Ω/1000 ft, 350 kcmil Aluminum — 0.0967 Ω/1000 ft, 500 kcmil Aluminum — 0.0678 Ω/1000 ft
- •Conductors per Phase — Options: 1 (Standard), 2 (Parallel), 3 (Parallel), 4 (Parallel)
Outputs
- •Voltage Drop (V)
- •Voltage Drop Percentage (%)
- •Voltage at Load (V)
Formula
Calculator Formula
This calculator estimates voltage drop using a resistance-based circuit model. The conductor resistance is expressed in ohms per 1000 ft.
Step 1: Effective Resistance
R_effective = R_conductor / N_conductors
Where R_conductor is the resistance per 1000 ft (Ω/1000 ft) for the selected conductor, and N_conductors is the number of parallel conductors per phase.
Step 2: Phase Factor
Single-Phase: Factor = 2
Three-Phase: Factor = √3 ≈ 1.732
Step 3: Voltage Drop
VD = (Factor × I × R_effective × L) / 1000
Where I = load current in amperes, and L = one-way length of run in feet.
Step 4: Voltage Drop Percentage
VD% = (VD / V_system) × 100
Step 5: Voltage at Load
V_load = V_system − VD
Variables
| Variable | Meaning | Units |
|---|---|---|
| V_system | Nominal system voltage | V |
| I | Load current | A |
| L | One-way wire length | ft |
| R_conductor | Conductor resistance per 1000 ft | Ω/1000 ft |
| N_conductors | Conductors per phase (parallel runs) | — |
| Factor | 2 for single-phase, √3 for three-phase | — |
| VD | Calculated voltage drop | V |
| VD% | Voltage drop as percentage of system voltage | % |
| V_load | Voltage delivered at the load | V |
Unit Handling
One-way wire length can be entered in feet (Imperial mode) or meters (Metric mode). When meters are entered, the value is converted to feet internally before applying the formula, since conductor resistance values are expressed in Ω/1000 ft per NEC Chapter 9 Table 8. All other inputs and outputs — voltage, current, resistance, and percentage — remain the same regardless of unit mode.
What is Voltage Drop
Voltage drop is the reduction in voltage that occurs as current flows through a conductor with resistance. In real electrical systems, voltage drop matters because a circuit can still be acceptable from an ampacity perspective yet still perform poorly if too much voltage is lost between the source and the load. That is why voltage-drop review is a common part of circuit design, especially for longer runs, higher currents, or smaller conductors.
The calculator converts conductor resistance, current, and one-way run length into a dropped voltage, then shows how much system voltage is actually left at the load. NEC informational notes commonly referenced in design practice point to about 3% branch-circuit drop and 5% total feeder-plus-branch drop as reasonable efficiency guidance.
Units
This calculator uses volts (V) for system voltage, voltage drop, and final load voltage; amperes (A) for load current; feet (ft) in Imperial mode or meters (m) in Metric mode for one-way length of run; ohms per 1000 ft (Ω/1000 ft) for conductor resistance; and percent (%) for voltage drop percentage. Unlike the dedicated NEC Copper and NEC Aluminum versions, this general calculator includes both copper and aluminum conductor options in a single dropdown, making it easy to compare materials side by side.
Practical Tips
Always enter the one-way distance, not the round-trip distance. The formula already accounts for the return path. When voltage drop exceeds 3%, consider upsizing the conductor before adding parallel conductors — it is often more cost-effective for moderate increases.
Remember that voltage drop and ampacity are separate requirements. A wire that passes the voltage drop check may still need to be upsized for ampacity, especially in high-temperature environments or conduits with many conductors.
Important: This calculator provides practical estimates using a resistance-based model. Final wire sizing must account for ampacity, temperature rating, conduit fill, power factor, and local code requirements.
Key Facts
- This calculator uses a resistance-based method — it starts with the selected conductor resistance and the entered run conditions, then calculates actual dropped voltage, percentage drop, and final load voltage.
- Percentage voltage drop is usually the primary result, while voltage drop in volts and final load voltage are supporting outputs.
- The NEC recommends (but does not require) a maximum 3% voltage drop on branch circuits and 5% total from service entrance to farthest outlet.
- One-way length is used because the system multiplier (2 for single-phase, √3 for three-phase) already accounts for the circuit path.
- Lower voltage drop is generally better, but the result should be read as design guidance, not automatic proof of compliance or violation.
- Using parallel conductors per phase effectively reduces the resistance and voltage drop proportionally.
- Wire resistance increases with temperature — the resistance values used here are based on 75°C conductor temperature per NEC Chapter 9 Table 8.
Applications
- Branch-circuit voltage drop review for residential and commercial installations.
- Feeder voltage drop review for panel-to-panel runs.
- Comparing conductor options across copper and aluminum materials side by side.
- Long-run circuit planning where voltage drop is a primary design concern.
- Checking whether voltage drop is likely acceptable before installation.
- Reviewing low-voltage conditions at the load.
- Conductor upsizing decisions based on voltage drop results.
- Preliminary circuit design screening for new construction and renovation projects.
Example Calculation
Example Calculation — Single-Phase
Given:
- System voltage = 120 V
- Phase = Single-phase
- Load current = 20 A
- One-way wire length = 150 ft
- Conductor resistance = 2.0 Ω/1000 ft
- Conductors per phase = 1
Step 1: Effective Resistance
R_effective = 2.0 / 1 = 2.0 Ω/1000 ft
Step 2: Phase Factor
Factor = 2 (single-phase)
Step 3: Voltage Drop
VD = (2 × 20 × 2.0 × 150) / 1000 = 12.0 V
Step 4: Voltage Drop Percentage
VD% = (12.0 / 120) × 100 = 10.0%
Step 5: Voltage at Load
V_load = 120 − 12.0 = 108.0 V
Interpretation: A voltage drop of 10.0% is well above common practical design guidance. In a case like this, the circuit would usually benefit from a larger conductor, a shorter run, or further design review rather than being accepted as-is. This example also shows why the general calculator is useful: even without locking the page to a specific copper-only or aluminum-only method, the resistance-based result still makes the design issue obvious. Practical NEC-style guidance commonly points to about 3% branch-circuit drop and 5% total system drop as a reasonable target for efficient operation.
Example 2 — Three-Phase
Given:
- System voltage = 480 V
- Phase = Three-phase
- Load current = 100 A
- One-way wire length = 200 ft
- Conductor resistance = 0.122 Ω/1000 ft (1/0 AWG Copper)
- Conductors per phase = 1
Step 1: Effective Resistance
R_effective = 0.122 / 1 = 0.122 Ω/1000 ft
Step 2: Phase Factor
Factor = 1.732 (three-phase)
Step 3: Voltage Drop
VD = (1.732 × 100 × 0.122 × 200) / 1000 = 4.23 V
Step 4: Voltage Drop Percentage
VD% = (4.23 / 480) × 100 = 0.88%
Step 5: Voltage at Load
V_load = 480 − 4.23 = 475.77 V
Interpretation: The voltage drop is only 0.88%, well within the NEC-recommended 3% guideline. This result confirms the conductor selection provides comfortable margin for this 480 V feeder run.
Standards & References
- NEC Chapter 9, Table 8 — DC resistance values for conductors (copper and aluminum, 75°C)
- NEC 210.19(A) Informational Note No. 4 — Recommends branch circuit voltage drop not exceed 3%
- NEC 215.2(A) Informational Note No. 2 — Recommends feeder voltage drop not exceed 3%, with total not exceeding 5%
- NEC 310.16 — Allowable ampacities for insulated conductors
- IAEI Voltage Drop Reference — Identifies resistance-based methods as generally acceptable for voltage-drop calculations
- IEEE Std 141 (Red Book) — Recommended practice for electric power distribution, including voltage drop considerations
Limitations
- This calculator is a practical voltage-drop tool, not a full conductor-design or installation-approval system.
- It does not replace conductor ampacity review, insulation temperature limits, equipment nameplate requirements, or local code enforcement.
- It assumes the selected conductor resistance value is appropriate for the scenario being evaluated.
- It does not account for power factor, which affects voltage drop in AC circuits with reactive loads.
- Conductor temperature is assumed at 75°C per NEC Chapter 9 Table 8 — actual resistance varies with operating temperature.
- Results are estimates for planning purposes — final design should consider all installation-specific factors including harmonics, conduit fill, and ambient temperature.
Common Mistakes to Avoid
- Entering round-trip length instead of one-way length — the formula already accounts for the return path with the factor of 2 or √3.
- Confusing ampacity compliance with voltage-drop quality — a conductor can still be acceptable for ampacity yet produce too much voltage drop for good system performance.
- Ignoring whether the review covers only the branch circuit or the combined feeder-plus-branch total.
- Assuming every voltage-drop calculator uses the same material constants or conductor assumptions — this page uses a general resistance-based model distinct from the NEC Copper and NEC Aluminum K-factor pages.
- Forgetting to account for parallel conductors when multiple conductors per phase are installed.
- Applying the 3% voltage drop guideline as a mandatory code requirement rather than an informational recommendation.
- Not verifying that the selected wire size also meets ampacity requirements — voltage drop and ampacity are separate checks.
Frequently Asked Questions
What does this Voltage Drop Calculator calculate?
What formula does this calculator use?
Why does voltage drop matter if ampacity is already acceptable?
Does NEC require exactly 3% voltage drop?
Should I enter one-way length or round-trip length?
Can this calculator replace conductor ampacity review?
What should I do if the voltage drop is too high?
Frequently Used Together
Engineers often use these calculators in combination for complete project workflows:
Related Calculators
Explore similar calculators that might be useful for your project:
Every Electrical Formula. One Free Sheet.
NEC calcs, motor sizing & code coordination — one printable page.
- Instantly check voltage drop, ampacity & motor current
- Catch the 7 wiring errors that fail code inspections
- 12 design checks to run before submitting drawings
No spam. Unsubscribe any time.
Calculate
Select the nominal system voltage for the circuit
Select single-phase or three-phase circuit configuration
Enter the expected load current in amperes
Enter the one-way distance from the panel to the load
Select conductor size and material — resistance values in ohms per 1000 ft (NEC Chapter 9 Table 8, 75°C)
Number of conductors per phase (parallel runs reduce effective resistance)