Voltage Drop Calculator — NEC (Copper)
On this page
Calculate
Select the nominal system voltage for the circuit
Select single-phase or three-phase circuit configuration
Enter the expected load current in amperes
Enter the one-way distance from the panel to the load
Select wire gauge — resistance values from NEC Ch.9 Table 8 (uncoated copper, Ω/km)
Number of conductors per phase (parallel runs reduce effective resistance)
Overview
A Voltage Drop Calculator helps determine the voltage lost across a conductor due to its resistance when carrying current over a given distance. This calculator uses NEC Chapter 9 Table 8 DC resistance values for uncoated copper conductors to estimate voltage drop for both single-phase and three-phase circuits.
Voltage drop is a critical consideration in electrical design because excessive drop can cause equipment malfunction, reduced efficiency, and code compliance issues. The NEC recommends — though does not mandate — that voltage drop on branch circuits not exceed 3%, and that total voltage drop from service entrance to the farthest outlet not exceed 5%.
This calculator is intended as a practical estimation tool for circuit planning, wire sizing verification, and preliminary electrical design. It does not replace detailed engineering analysis that accounts for conductor temperature, conduit fill, ambient conditions, or AC impedance effects.
How to Use This Calculator
Select system voltage — choose from 120 V, 208 V, 240 V.
Select phase configuration — choose from Single-Phase, Three-Phase.
Enter load current — in A.
Enter one-way wire length — in m or ft.
Select wire size (awg/kcmil) — choose from 14 AWG, 12 AWG, 10 AWG.
Select conductors per phase — choose from 1, 2, 3.
Click "Calculate" — get voltage drop, voltage drop percentage, voltage at load.
Use the result to support your engineering design and analysis decisions.
Inputs & Outputs
Inputs
- •System Voltage — Options: 120 V, 208 V, 240 V, 277 V, 480 V, 600 V
- •Phase Configuration — Options: Single-Phase, Three-Phase
- •Load Current (A)
- •One-Way Wire Length (m / ft)
- •Wire Size (AWG/kcmil) — Options: 14 AWG, 12 AWG, 10 AWG, 8 AWG, 6 AWG, 4 AWG, 3 AWG, 2 AWG, 1 AWG, 1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil, 500 kcmil, 600 kcmil, 750 kcmil
- •Conductors per Phase — Options: 1 (Standard), 2 (Parallel), 3 (Parallel), 4 (Parallel)
Outputs
- •Voltage Drop (V)
- •Voltage Drop Percentage (%)
- •Voltage at Load (V)
Formula
Calculator Formula
This calculator estimates voltage drop using DC resistance values from NEC Chapter 9 Table 8 for uncoated copper conductors.
Step 1: Effective Resistance
R_effective = R_wire / N_conductors
Where R_wire is the resistance per 1000 m (Ω/km) for the selected wire gauge, and N_conductors is the number of parallel conductors per phase.
Step 2: Phase Factor
Single-Phase: Factor = 2
Three-Phase: Factor = √3 ≈ 1.732
Step 3: Voltage Drop
Vd = Factor × I × L × R_effective / 1000
Step 4: Voltage Drop Percentage
Vd% = (Vd / V_system) × 100
Step 5: Voltage at Load
V_load = V_system − Vd
Variables
| Variable | Meaning | Units |
|---|---|---|
| V_system | Nominal system voltage | V |
| I | Load current | A |
| L | One-way wire length | m (ft converted internally) |
| R_wire | Wire resistance per NEC Ch.9 Table 8 | Ω/km |
| N_conductors | Conductors per phase (parallel runs) | — |
| Factor | 2 for single-phase, √3 for three-phase | — |
| Vd | Calculated voltage drop | V |
| Vd% | Voltage drop as percentage of system voltage | % |
| V_load | Voltage delivered at the load | V |
What is Voltage Drop
Voltage drop is the reduction in voltage that occurs as electrical current flows through a conductor. Every conductor has some resistance, and that resistance causes a portion of the supply voltage to be consumed along the wire rather than delivered to the load. The longer the wire run and the smaller the conductor, the greater the voltage drop.
Excessive voltage drop can cause lights to dim, motors to overheat, and sensitive equipment to malfunction. That is why voltage drop analysis is a standard part of electrical circuit design, even though the NEC treats the 3% and 5% guidelines as informational recommendations rather than mandatory requirements.
Key Facts
- Voltage drop is caused by the resistance of the conductor — longer runs and smaller wire sizes produce more drop.
- The NEC recommends (but does not require) a maximum 3% voltage drop on branch circuits and 5% total from service entrance to farthest outlet.
- Using parallel conductors per phase effectively reduces the resistance and voltage drop proportionally.
- Copper conductors have lower resistance than aluminum for the same wire gauge, resulting in less voltage drop.
- The factor of 2 for single-phase accounts for current flowing through both the hot and neutral conductors.
- For three-phase circuits, the √3 (1.732) factor replaces the factor of 2 used in single-phase calculations.
- Wire resistance increases with temperature — NEC Table 8 values are based on 75°C conductor temperature.
Applications
- Branch circuit wire sizing verification for residential and commercial installations.
- Feeder circuit voltage drop estimation for panel-to-panel runs.
- Long-run circuit planning where voltage drop is a primary design concern.
- Comparing wire gauge options to find the most cost-effective size that meets voltage drop targets.
- Preliminary electrical design for new construction and renovation projects.
- Evaluating whether parallel conductors are needed to reduce voltage drop on high-current circuits.
- Educational reference for electricians, contractors, and engineering students.
Example Calculation
Example Calculation — Single-Phase
Given:
- System voltage = 240 V
- Phase = Single-phase
- Load current = 40 A
- One-way wire length = 30 m (≈ 100 ft)
- Wire size = 8 AWG (R = 3.18 Ω/km)
- Conductors per phase = 1
Step 1: Effective Resistance
R_effective = 3.18 / 1 = 3.18 Ω/km
Step 2: Phase Factor
Factor = 2 (single-phase)
Step 3: Voltage Drop
Vd = 2 × 40 × 30 × 3.18 / 1000 = 7.63 V
Step 4: Voltage Drop Percentage
Vd% = (7.63 / 240) × 100 = 3.18%
Step 5: Voltage at Load
V_load = 240 − 7.63 = 232.37 V
Interpretation: The voltage drop is 3.18%, which slightly exceeds the NEC-recommended 3% guideline for branch circuits. Consider upsizing to 6 AWG to reduce the drop below 3%.
Example 2 — Three-Phase
Given:
- System voltage = 480 V
- Phase = Three-phase
- Load current = 100 A
- One-way wire length = 60 m (≈ 200 ft)
- Wire size = 1/0 AWG (R = 0.319 Ω/km)
- Conductors per phase = 1
Step 1: Effective Resistance
R_effective = 0.319 / 1 = 0.319 Ω/km
Step 2: Phase Factor
Factor = 1.732 (three-phase)
Step 3: Voltage Drop
Vd = 1.732 × 100 × 60 × 0.319 / 1000 = 3.31 V
Step 4: Voltage Drop Percentage
Vd% = (3.31 / 480) × 100 = 0.69%
Step 5: Voltage at Load
V_load = 480 − 3.31 = 476.69 V
Interpretation: The voltage drop is only 0.69%, well within the NEC-recommended 3% guideline. The 1/0 AWG copper conductor is well-suited for this circuit.
Standards & References
- NEC Chapter 9, Table 8 — DC resistance values for conductors (uncoated copper, 75°C)
- NEC 210.19(A) Informational Note No. 4 — Recommends branch circuit voltage drop not exceed 3%
- NEC 215.2(A) Informational Note No. 2 — Recommends feeder voltage drop not exceed 3%, with total not exceeding 5%
- NEC 310.16 — Allowable ampacities for insulated conductors
- IEEE Std 141 (Red Book) — Recommended practice for electric power distribution, including voltage drop considerations
Limitations
- This calculator uses DC resistance values from NEC Chapter 9 Table 8 — actual AC impedance may differ due to skin effect and conduit material.
- It does not account for power factor, which affects voltage drop in AC circuits with reactive loads.
- Conductor temperature is assumed at 75°C per NEC Table 8 — actual resistance varies with operating temperature.
- The calculator does not verify conductor ampacity — wire sizing for ampacity must be checked separately.
- It does not account for voltage drop in the neutral conductor for unbalanced three-phase loads.
- Results are estimates for planning purposes — final design should consider all installation-specific factors.
Common Mistakes to Avoid
- Using round-trip distance instead of one-way distance (the formula already accounts for the return path with the factor of 2 or √3).
- Confusing wire gauge resistance values between copper and aluminum conductors.
- Forgetting to account for parallel conductors when multiple conductors per phase are installed.
- Using AC impedance values when DC resistance values are more appropriate for simple voltage drop estimates, or vice versa.
- Ignoring voltage drop entirely and sizing wire only for ampacity, which can result in poor equipment performance.
- Applying the 3% voltage drop guideline as a mandatory code requirement rather than an informational recommendation.
- Not verifying that the selected wire size also meets ampacity requirements — voltage drop and ampacity are separate checks.
Frequently Asked Questions
What does this Voltage Drop Calculator calculate?
What is an acceptable voltage drop?
Why does the calculator use a factor of 2 for single-phase?
Why does three-phase use √3 instead of 2?
Does this calculator account for AC impedance?
Can I use this for aluminum conductors?
What does 'conductors per phase' mean?
Should I enter round-trip or one-way distance?
Frequently Used Together
Engineers often use these calculators in combination for complete project workflows:
Related Calculators
Explore similar calculators that might be useful for your project:
Every Electrical Formula. One Free Sheet.
NEC calcs, motor sizing & code coordination — one printable page.
- Instantly check voltage drop, ampacity & motor current
- Catch the 7 wiring errors that fail code inspections
- 12 design checks to run before submitting drawings
No spam. Unsubscribe any time.
Calculate
Select the nominal system voltage for the circuit
Select single-phase or three-phase circuit configuration
Enter the expected load current in amperes
Enter the one-way distance from the panel to the load
Select wire gauge — resistance values from NEC Ch.9 Table 8 (uncoated copper, Ω/km)
Number of conductors per phase (parallel runs reduce effective resistance)